ABB REO 517 Applications Manual page 134

Multi-function terminals for railway application
Table of Contents

Advertisement

TEST
Block BFP=Yes
TEST-ACTIVE
BFP-BLOCK
STIL1
BFP-START
STIL2
RETRIP=I>Check
RETRIP=No I>Check
124
Breaker failure protection (BFP)
&
≥1
&
&
)LJXUH  %UHDNHUIDLOXUH SURWHFWLRQ VLPSOLILHG ORJLF GLDJUDP
The application functions of the protection are:
Individual phase-current detection
Two time steps, one for retrip of the related circuit breaker and one for the back-up
trip of the adjacent circuit breakers
Selection of current controlled or unconditional retrip
Phase separated timers gives correct operation at an evolving fault
Accurate timers and current elements reset in 10 ms, allowing the use of short back-
up trip time
t2
t
t1
&
t
&
t2
t
&
&
&KDSWHU 
tp
≥1
BFP-TRBU
tp
≥1
BFP-TRRET
tp
t1
t
en02000543.v sd
&XUUHQW