&KDSWHU 
Scheme communication logic for residual
overcurrent protection (EFC)
&XUUHQW
%ORFNLQJ VFKHPH
In the blocking scheme, set the tCoord timer to the channel transmission time during
disturbance conditions. Add a margin of 20-30 ms. Two times the nominal value of the
channel transmission time is recommended when a power line carrier is used.
3HUPLVVLYH FRPPXQLFDWLRQ VFKHPH
In the permissive communication scheme, the security against unwanted operation
caused by spurious carrier receive signals can be increased by delaying the tripping out-
put with the tCoord timer. Set the timer in the range of 0.000 to 60.000 s. In most cases,
a time delay of 30 ms is sufficient.