354
Monitoring of DC analog measurements
Remotely over the SPA port to the station monitoring system (SMS)
8VHUGHILQHG PHDVXULQJ UDQJHV
The measuring range of different direct current measuring channels is settable by the
user independent on each other within the range between -25 mA and +25 mA in steps
of 0.01 mA. It is only necessary to select the upper operating limit I_Max higher than
the lower one I_Min.
The measuring channel can have a value of 2 of the whole range I_Max - I_Min above
the upper limit I_Max or below the lower limit I_Min, before an out-of-range error oc-
curs. This means that with a nominal range of 0-10 mA, no out-of-range event will oc-
cur with a value between -0.2 mA and 10.2 mA.
User can this way select for each measuring quantity on each monitored object of a
power system the most suitable measuring range and this way optimize a complete
functionality together with the characteristics of the used measuring transducer.
&RQWLQXRXV PRQLWRULQJ RI WKH PHDVXUHG TXDQWLW\
The user can continuously monitor the measured quantity in each channel by means of
six built-in operating limits (figure 190). Two of them are defined by the operating
range selection: I_Max as the upper and I_Min as the lower operating limit. The other
four operating limits operate in two different modes:
Overfunction, when the measured current exceeds the HiWarn or HiAlarm pre-set
values
Underfunction, when the measured current decreases under the LowWarn or Low-
Alarm pre-set values
&KDSWHU 
0RQLWRULQJ