Monitoring of AC analog measurements
Users can select between two types of dead-band supervision:
Amplitude dead-band supervision (ADBS).
Integrating dead-band supervision (IDBS).
$PSOLWXGH GHDGEDQG VXSHUYLVLRQ
If a measuring value is changed, compared to the last reported value, and the change is
larger than the +/- ∆ Y predefined limits that are set by user, then the measuring channel
reports the new value to a higher level, if this is detected by a new measuring sample.
This limits the information flow to a minimum necessary. Figure 183 shows an example
of periodic reporting with the amplitude dead-band supervision. The picture is simpli-
fied: the process is not continuous but the values are evaluated with a time interval of
one second from each others.
<
Value Reported
(1st)
<
)LJXUH $PSOLWXGH GHDGEDQG VXSHUYLVLRQ UHSRUWLQJ
After the new value is reported, the +/- ∆ Y limits for dead-band are automatically set
around it. The new value is reported only if the measured quantity changes more than
defined by the +/- ∆ Y set limits.
,QWHJUDWLQJ GHDGEDQG VXSHUYLVLRQ
The measured value is reported if the time integral of all changes exceeds the pre-set
limit (figure 184), where an example of reporting with integrating dead-band supervi-
sion is shown. The picture is simplified: the process is not continuous but the values are
evaluated with a time interval of one second from each other.
Value Reported
Value Reported
<
∆Y
∆Y
<
∆Y
∆Y
∆Y
∆Y
&KDSWHU 
0RQLWRULQJ
Value Reported
W
99000529.vsd
341