ABB REO 517 Applications Manual page 282

Multi-function terminals for railway application
Table of Contents

Advertisement


272
Interlocking
&RQILJXUDWLRQ
The signals from other bays connected to the module BB_ES are described below.
6LJQDOV LQ VLQJOH EUHDNHU DUUDQJHPHQW
The busbar earthing switch is only allowed to operate if all disconnectors of the bus sec-
tion are open.
Section 1
A1
B1
C
BB_ES
ABC_LINE
)LJXUH  %XVEDUV GLYLGHG E\ EXVVHFWLRQ GLVFRQQHFWRUV FLUFXLW EUHDNHUV
To derive the signals:
6LJQDO
ABCDC_OP
Signal if all disconnectors of this busbar section are open.
VP_ABCDC
The switch status of ABCDC is valid.
EXDUP_BB
Signal if no transmission error from any bay containing the above informa-
tion.
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),
and each bus-coupler bay (ABC_BC) are needed:
6LJQDO
Q1OPTR
Signal if Q1 is open.
Q2OPTR
Signal if Q2 (AB_TRAFO, ABC_LINE) is open.
Q20OPTR
Signal if Q2 and Q20 (ABC_BC) are open.
Q7OPTR
Signal if Q7 is open.
VPQ1TR
The switch status of Q1 is valid.
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
AB_TRAFO ABC_LINE
&KDSWHU 
Section 2
A2
B2
C
BB_ES
99000384.vsd
&RQWURO