General-purpose input function parameters

This section explains the general-purpose input parameters.
Set the input response time parameters in GX Works3.
Parameter setting
This section explains how to set the input response time parameters.
Set the input response time.
Navigation window  [Parameter]  [FX5UCPU]  [Module Parameter]  [Input Response Time]
Window
Displayed items
Item
Description
Response Type
Select the input response time between 1 point unit and 8
point unit.
High-Speed: Unit of 1 point
Normal: Unit of 8 points
X0 to X377
Set the input response time.
Parameters are enabled when the CPU module is powered ON or after a reset.
Setting range
• High-Speed
• Normal
• No Setting
• 10micro-s (μs)
• 50micro-s (μs)
• 0.1ms
• 0.4ms
• 0.6ms
• 1ms
• 5ms
• 10ms
• 20ms
• 70ms
24 HIGH-SPEED INPUT/OUTPUT FUNCTION
24.6 General-purpose Input Functions
24
Default
10ms