Target Data; Number Of Data Points; Data Type; Data To Be Collected - Mitsubishi Electric FX5 User Manual

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

19.1

Target Data

This section describes the data to be collected by data logging.

Number of data points

The data logging function can collect up to 512 data records. (4 settings × 128 records)
*1 Duplicate data records are counted as unique records.

Data type

The following table shows the number of data records for each data type.
Data type
Bit
Word (signed)
Double word (signed)
Word (unsigned)
Double word (unsigned)
Single-precision real number
Time
*1*2
String
*2
Numeric string
*1 Outputs the entered character code.
*2 Collected as binary data.
*3 The specified size can be 1 to 256. If the specified size is an odd number, the number of data records is rounded to the next higher
integer. Example: The number of data records is 3 if the specified size is 5.

Data to be collected

The data for the following devices can be specified to be collected.
Type
*2
Bit device
*3
Word device
Double-word device
*1 Index modification, and indirect specification cannot be specified.
*2 For bit devices, bit specification of word cannot be specified.
*3 For word devices, nibble specification of bit devices cannot be specified.
*4 To specify these devices with the CPU Module Logging Configuration Tool, use T (contact): TS, T (coil): TC, ST (contact): STS, ST (coil):
STC, C (contact): CS, C (coil): CC, LC (contact): LCS, and LC (coil): LCC.
*5 To specify these devices with the CPU Module Logging Configuration Tool, use T (current value): T or TN, ST (current value): ST or
STN, C (current value): C or CN, and LC (current value): LC or LCN.
*1
Device
*4
X, Y, M, SM, L, B, F, SB, T (contact)
*4
(coil)
*5
T (current value)
, ST (current value)
*5
LC (current value)
*1
Data number of points
1
1
2
1
2
2
2
*3
Specified size/2
*3
Specified size/2
*4
*4
*4
, T (coil)
, ST (contact)
, ST (coil)
*5
*5
, C (current value)
, D, SD, W, SW, R, U\G
19 DATA LOGGING FUNCTION
*4
*4
, C (contact)
, C (coil)
, LC (contact)
19.1 Target Data
19
*4
, LC
129

Advertisement

Table of Contents
loading