Mitsubishi Electric FX5 User Manual page 207

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

■High-speed pulse input/output module
Add the high-speed pulse input/output module.
Navigation window  [Parameter]  [Module Information]  Right-click  Add New Module
After adding the high-speed pulse input/output module, make settings on the the screen displayed from the following
operation.
Navigation window  [Parameter]  [Module Information]  [1 to 16 (high-speed pulse input/output module)] 
[Module Parameter]  "Input Function"  "High Speed Counter"  "Detailed Setting"  "High Speed Compare Table"
Window
Shown above is the screen at the time when the first high-speed pulse input/output module is selected.
Displayed items
Item
Description
Counter CH
Set the counter CH of coincidence output target.
Comparison Type
Set comparison type.
Output Destination Device
Sets output destination device for output comparison
results of comparison value 1 and comparison value 2.
Comparison Value 1
Sets the specification method of comparison value 1.
Specification Method
Comparison Value 1 Direct
Sets value (comparison value 1) to be compared with
current value of high-speed counter. (When direct
specification is selected)
Comparison Value 1 Indirect
Sets device (comparison value 1) to be compared with
current value of high-speed counter. (When indirect
specification is selected)
*1 The number in  is first module: 9, second module: 11, third module: 13, fourth module: 15.
• You can create an open table entry before table setting is complete.
• Table settings can be made in any order. Be careful when the current value is changed by self-reset at a
table along the way, as table processing starts with the first table then the following tables in order.
High-speed comparison table operation
Operation of each type of high-speed comparison table operation is explained below.
■Set to ON
When comparison value 1 matches the current value of the set high-speed counter, the bit device specified as the output
destination device is set. If interrupt pointer has been specified for output destination device, the interrupt program of the
specified interrupt pointer is run simultaneously when it matches comparison value 1.
Operation is the same as for the DHSCS instruction. For information on the DHSCS instruction, refer to MELSEC iQ-F
FX5 Programming Manual (Instructions, Standard Functions/Function Blocks).
■Reset
When comparison value 1 matches the current value of the set high-speed counter, the bit device specified as the output
destination device is reset.
Operation is the same as for the DHSCR instruction. For information on the DHSCR instruction, refer to MELSEC iQ-F
FX5 Programming Manual (Instructions, Standard Functions/Function Blocks).
Setting range
Disable, CH+0(CH),CH+1(CH+1)
• Set
• Reset
• Self Reset
Bit device (Y, M), Interrupt pointer (I50 to I177)
• Direct Specification
• Indirect Specification
-2147483648≤Comparison value 1≤+2147483647
Word device (D, R)
24 HIGH-SPEED INPUT/OUTPUT FUNCTION
24.1 High-speed Counter Function
Default
*1
Disable
Set
Direct
Specificati
on
0
205
24

Advertisement

Table of Contents
loading

Table of Contents