Mitsubishi Electric FX5 User Manual page 435

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

Error
Error name
Error details and cause
code
413BH
File related error
• The same file was simultaneously accessed from different
engineering tools.
■When CPU Module Logging Configuration Tool is used
• An operation was performed to a file being accessed.
413EH
File related error
• Operation is disabled for the specified drive (memory).
4180H
CPU module
• A system error or setting data error in the OS (Malfunctions
built-in Ethernet
caused by noise and hardware failure are possible causes.)
port error
4181H
CPU module
• Transmission to the receiving modules is unsuccessful.
built-in Ethernet
port error
4183H
CPU module
• Communication with receiving modules was interrupted.
built-in Ethernet
port error
419AH
CPU module
• A system error or setting data error in the OS (Malfunctions
built-in Ethernet
caused by noise and others and hardware failure are the
port error
possible causes.)
419EH
CPU module
• Connection to the module was unsuccessful or interrupted.
built-in Ethernet
port error
41C5H
File related error
• The specified file does not exist.
■When CPU Module Logging Configuration Tool is used
• When an attempt was made to re-register the data logging
with the previous settings, the corresponding file did not
exist.
41C8H
File related error
• The size of the specified file has exceeded that of the
existing file.
41CCH
File related error
• The specified file does not exist. Or, the specified
subdirectory does not exist.
■When CPU Module Logging Configuration Tool is used
• The data logging was started in a state that sub-folders for
storing data logging files (or folders) cannot be created or
accessed. Or, sub-folders cannot be created or accessed
while the data logging is being performed or the logged data
is being saved.
Action
• Execute again after a while.
• Execute again after changing the target drive (memory).
• Confirm that the power supply module and CPU module is
mounted correctly.
• Confirm that the usage environment of the system is in the
ranges of the generic specifications for the CPU module.
• Confirm that the power supply capacity is enough.
• Reset the CPU module.
• If the same error appears, the hardware of the CPU module
may be malfunctioning. Consult your local Mitsubishi
Electric representative. If an error occurs again after the
above confirmation and corrective actions, hardware failure
of the CPU module is a possible cause.
• Check the external device operation.
• Check the status of the lines, such as cables, hubs and
routes, connected to receiving modules.
• Some line packets may be engaged. Retry to communicate
a little while later.
• The receiving module may have no free space in receive
area (TCP window size is small). Check whether the
receiving module processes receive data, or whether the
CPU module does not send unnecessary data.
• Check whether the settings of the subnet mask pattern and
the default router IP address of the CPU module and the
receiving modules are correct, or whether the class of the IP
address is correct.
• Check the external device operation.
• Check the status of the lines such as cables, hubs and
routes connected to receiving modules.
• Error may be generated when connection is forcibly
canceled during communication. In that case, there is no
issue, so clear the error.
• Check the external device operation.
• Check the status of the lines such as cables, hubs and
routes connected to receiving modules.
• The error may be generated when connection is forcibly
canceled during communication. In that case, there is no
issue, so clear the error.
• Check the external device operation.
• Check the status of the lines such as cables, hubs and
routes connected to receiving modules.
• Retry to connect a little while later, if the error occurred in
communication.
• Execute again after checking the file.
• Execute again after checking the size of the specified file.
• If the error recurs after re-execution, the file information data
may be corrupted.
• Back up data in the CPU module, and then initialize the
memory.
• Execute again after checking the name of the file and
subdirectory.
Appendix 3 Error Code
A
APPX
433

Advertisement

Table of Contents
loading

Table of Contents