PWM output abnormal end flag
This device is for monitoring the end status (abnormal end) of PWM output.
■Corresponding devices
The device numbers corresponding to each channel are as follows.
CPU module
CH1
CH2
CH3
SM5332
SM5333
SM5334
■Update timing
The timing of device update is as follows.
ON
• At stop of pulse output due to an error in the setting value of the pulse width,
period, or output pulse count
• At stop of pulse output due to the relation of pulse width > period
• In the case of forced stop with SM8034 (all output disable) or output cannot
be started
The ON timing of the PWM output abnormal end flag includes startup of the PWM/DPWM, HIOEN/ DHIOEN
instruction.
Number of output pulses
The number of output pulses of PWM output is stored.
When "0" is set, output is continued without any limitation.
■Corresponding devices
The device numbers corresponding to each channel are as follows.
CPU module
CH1
CH2
CH3
SD5301,
SD5317,
SD5333,
SD5300
SD5316
SD5332
■Update timing
The timing to reflect the device in operation is as follows.
• When the HCMOV/DHCMOV instruction is executed (values updated immediately)
• When the PWM/DPWM instruction is executed
• END processing
■Clear timing
The timing when the device is cleared is as follows.
• STOP/PAUSE→RUN
• If the number of output pulses written is equal to or smaller than the number of pulses that have already
been output, pulse output is stopped after the pulses being currently output are completed.
• If the number of output pulses written is greater than the number of pulses that have already been output,
pulse output is stopped after the specified number of pulses are output.
• If the number of output pulses is set to "0" (output without any limitation), the value cannot be changed while
pulses are being output.
• The number of output pulses cannot be changed to "0" (output without any limitation) while pulses are being
output.
24 HIGH-SPEED INPUT/OUTPUT FUNCTION
294
24.7 PWM Function
High-speed pulse input/output module
First module
CH4
CH5
CH6
SM5335
SM5336
SM5337
High-speed pulse input/output module
First module
CH4
CH5
CH6
SD5349,
SD5365,
SD5381,
SD5348
SD5364
SD5380
Second module
Third module
CH7
CH8
CH9
SM5338
SM5339
SM5340
OFF
• Power OFF→ON, reset, STOP/PAUSE→RUN
• When pulse output starts
• When turned OFF by the user
• After forced stop by SM8034 (all output disable), SM8034 is turned off, and
PWM output resumes (only when unlimited output)
Second module
Third module
CH7
CH8
CH9
SD5397,
SD5413,
SD5429,
SD5396
SD5412
SD5428
Fourth module
CH10
CH11
CH12
SM5341
SM5342
SM5343
Fourth module
CH10
CH11
CH12
SD5445,
SD5461,
SD5477,
SD5444
SD5460
SD5476

Advertisement