Mitsubishi Electric FX5 User Manual page 412

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

Error
Error name
code
3057H
System bus error
3060H
System bus error
3061H
System bus error
3120H
Program error
3121H
Program error
3142H
Program
structure error
APPX
410
Appendix 3 Error Code
Error details and cause
• A timeout occurred during
communication with a connected module
during system processing.
• A signal error was detected with a
connected module when an instruction
was executed.
• A signal error was detected during
system processing.
• The CPU module does not support the
dedicated instruction executed.
• The dedicated instructions specified in
the program cannot be executed with the
specified module.
• The number of devices used in the
dedicated instruction specified in the
program is incorrect.
• The temporary area was used
incorrectly.
Action
• Verify that extension cables are correctly
connected.
• Verify that the version of the CPU module is
compatible with the module where the error
was detected.
• Implement anti-noise measures.
• If there is no problem, there may be a
malfunction in the connected module or in
the extension cables.
• When an error occurs alongside positioning
function, positioning may not stop at the
specified position. After removing the cause
of the system bus error, perform zero return
and clear error.
• Verify that extension cables are correctly
connected.
• Verify that the version of the CPU module is
compatible with the module where the error
was detected.
• Implement anti-noise measures.
• If there is no problem, there may be a
malfunction in the connected module or in
the extension cables.
• When an error occurs alongside positioning
function, positioning may not stop at the
specified position. After removing the cause
of the system bus error, perform zero return
and clear error.
• Verify that extension cables are correctly
connected.
• Verify that the version of the CPU module is
compatible with the module where the error
was detected.
• Implement anti-noise measures.
• If there is no problem, there may be a
malfunction in the connected module or in
the extension cables.
• When an error occurs alongside positioning
function, positioning may not stop at the
specified position. After removing the cause
of the system bus error, perform zero return
and clear error.
• Check the detailed information (error
location information) of the error by
executing module diagnostics using the
engineering tool, display the error program
(step) by the error jump, and correct the
program.
• Check the detailed information (error
location information) of the error by
executing module diagnostics using the
engineering tool, display the error program
(step) by the error jump, and correct the
program.
• Check the detailed information (error
location information) of the error by
executing module diagnostics using the
engineering tool, display the error program
(step) by clicking the [Error Jump] button,
and check the program. The step number
displayed in the error location information is
counted from the top of the file. (It may be
different from the step number in the
program displayed by the jump function.)
Detailed
Diagnostic
information
timing
System
At END
configuration
instruction
information
execution, at
interrupt
occurrence,
at module
access
Error location
At instruction
information
execution
System
At instruction
configuration
execution
information
Error location
At power-on,
information
at RESET, at
STOP →
RUN state, at
instruction
execution
Error location
At instruction
information
execution
Error location
At instruction
execution
information

Advertisement

Table of Contents
loading

Table of Contents