Appendix 3 Error Code
Error details and cause
• The specified command cannot be executed because the
communication setting reflection function of iQ Sensor
Solution is being executed.
• The specified command cannot be executed because the
monitor function of iQ Sensor Solution is being executed.
• The specified command cannot be executed because the
sensor parameter read/write function of iQ Sensor Solution
is being executed.
• Access to the specified station cannot be made since the
routing parameters are not set to the start source CPU
module and/or relay CPU module.
• The third byte of the IP address (network number) specified
by the IP communication test and the third byte of the IP
address of the CPU module that starts the IP
communication test are duplicated.
• The CPU module that performs IP packet transfer is not the
control CPU of the CC-Link IE module, which is on the path
that IP packets travel.
• The network of the number set to the routing parameters
does not exist.
• The specified CPU module cannot be communicated
through the network that is not supported by the CPU
module.
• Access to the specified station cannot be made.
• An error occurred in the access destination or relay station.
• The specified transfer setup (request destination module
number) is invalid.
• The request is not addressed to the CPU module.
• The specified route is not supported by the specified CPU
module version.
• There is not enough free space for storing the result file in
the target memory.
• The result file cannot be written to the target memory
because the SD memory card is write-protected or the
folder/file structure is incorrect.
• The SD memory card was removed while the data logging
function was being executed (data logging status:
Collecting, Trigger waiting (collecting before trigger),
Collecting after trigger, or Saving the logging data).
• The number of files in the root directory and subdirectory in
the target memory exceeded the limit.
• System error
• The maximum allowable capacity is exceeded.
• The maximum allowable number of files is exceeded.
• The upper limit of the backup folder number is exceeded.
• The maximum length (255 characters) of the file path is
exceeded.
Action
• Execute the command again after the communication
setting reflection processing ends.
• Execute the function again after a while.
• Execute the command again after the sensor parameter
read/write processing ends.
• Set to the related stations the routing parameters for access
to the specified station.
• Retry after a while. Or, start communication after checking
that the system for data routing has started.
• Do not duplicate the third byte of the IP address (network
number) specified by the IP communication test and the
third byte of the IP address of the CPU module that starts
the IP communication test.
• Set the CPU module that performs IP packet transfer as the
control CPU of the CC-Link IE module, which is on the path
that IP packets travel.
• Check and correct the routing parameters set to the related
stations.
• Set communication through the network that is supported by
the specified CPU module.
• Check the network module for error, or check that the
modules are not in offline.
• Check if the network numbers/PC numbers are correctly
set.
• Take corrective action after checking the error that occurred
at the specified access destination or the relay station to the
accessed station.
• Check the transfer setup (request destination module
number or PLC number) in the request data of SLMP/MC
protocol.
• Check the stop error, and take action.
• Perform operation to a module that can execute the
specified function.
• Check whether the specified route is supported or not.
• Check the stop error, and take action.
• Increase the free space, and create the result file again.
• Unlock the write protect switch of the SD memory card, and
write the result file again.
• Check that the SD memory card is not damaged.
• Check that files/folders used in the SD memory card are not
deleted.
• Insert the SD memory card, and execute the function again.
• Increase the free space of the drive (memory), and execute
the function again.
• Delete files in the drive (memory), and execute the function
again.
• Check the specified data, and write it to the CPU module
again.
• Increase the free space of the SD memory card and CPU
module, and execute the function again.
• Delete files in the SD memory card and CPU module, and
execute the function again.
• Delete backup data in the SD memory card and CPU
module, and execute the function again.
• Check and correct the folder structure or folder/file names of
backup target data, and execute the data backup function
again.