Error
Error name
Error details and cause
code
1829H
Write during RUN
• Writing during RUN (change or deletion)
error (axis 9)
is performed on an instruction being
executed.
1830H
Write during RUN
• Writing during RUN (change or deletion)
error (axis 10)
is performed on an instruction being
executed.
1831H
Write during RUN
• Writing during RUN (change or deletion)
error (axis 11)
is performed on an instruction being
executed.
1832H
Write during RUN
• Writing during RUN (change or deletion)
error (axis 12)
is performed on an instruction being
executed.
1900H
Constant scan
• The scan time exceeded the constant
time error
scan setting value.
1912H
Update error
• Recovery of the project data saved in the
SD memory card failed.
1920H
IP address
• Values such as the IP address setting
setting error
(SD8492 to SD8497) are outside the set
range.
1921H
IP address
• Write request and clear request (M8492
writing/clear
and SM8495) turned from OFF to ON
request
simultaneously.
simultaneous
detection
1930H
Online change
• An error was detected when writing was
error
executed during RUN.
1931H
Online change
• An error was detected when writing was
error
executed during RUN.
1FE0H
Module
• The number of I/O points specified in the
configuration
I/O assignment setting of the parameters
error
is different from that of the module
connected.
1FE1H
Module
• The module position specified in the I/O
configuration
assignment setting of the parameters is
error
different from that of the module
connected.
1FE2H
Module
• No parameters available for the module
configuration
connected exist.
error
Action
• Verify that the writing during RUN (change or
deletion) is performed on an instruction
being executed.
• If the writing is executed during an ongoing
RUN, after confirming that the pulse output
is not occurring, turn OFF → ON the driving
contact point to start the operation of the
positioning instruction.
• Verify that the writing during RUN (change or
deletion) is performed on an instruction
being executed.
• If the writing is executed during an ongoing
RUN, after confirming that the pulse output
is not occurring, turn OFF → ON the driving
contact point to start the operation of the
positioning instruction.
• Verify that the writing during RUN (change or
deletion) is performed on an instruction
being executed.
• If the writing is executed during an ongoing
RUN, after confirming that the pulse output
is not occurring, turn OFF → ON the driving
contact point to start the operation of the
positioning instruction.
• Verify that the writing during RUN (change or
deletion) is performed on an instruction
being executed.
• If the writing is executed during an ongoing
RUN, after confirming that the pulse output
is not occurring, turn OFF → ON the driving
contact point to start the operation of the
positioning instruction.
• Check and correct the constant scan time
setting. Recheck the setting time of the
constant scan.
• Recovery of the project data failed, so
initialize all data, and then write in the set of
project data backed up by the customer.
• Recheck the values such as the IP address
setting (SD8492 to SD8497).
• Verify that write request and clear request
(SM8492 and MS8495) do not turn from
OFF to ON simultaneously.
• Set the CPU module to STOP and write a set
of project data.
• Set the CPU module to STOP and write a set
of project data.
• Make sure that the parameters are
consistent with the connections.
• Make sure that the parameters are
consistent with the connections.
• Make sure that the parameters are
consistent with the connections.
Detailed
Diagnostic
information
timing
Error location
At END
information
instruction
and system
execution
configuration
information
Error location
At END
information
instruction
and system
execution
configuration
information
Error location
At END
information
instruction
and system
execution
configuration
information
Error location
At END
information
instruction
and system
execution
configuration
information
Time
At END
information
instruction
execution
Drive/file
At power-on,
information
at RESET
At END
instruction
execution
At END
instruction
execution
At END
instruction
execution
At END
instruction
execution
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
APPX
403
Appendix 3 Error Code
A

Advertisement

Table of Contents
loading

Table of Contents