■When keeping in forced ON or OFF status in advance
When keeping in forced ON or OFF status in advance, interlock using the PAUSE contact (SM204).
M20
X0
SM204
M0
SM204
12.3

Remote RESET

This is an operation to reset the CPU module by an external operation when the CPU module is in the STOP status. In
addition, even if the RUN/STOP/RESET switch of the CPU module is set to RUN position, reset is possible when the CPU
module has stopped due to occurrence of an error that can be detected by self-diagnosis function.

Application of remote RESET

When a CPU module is in an inaccessible place and an error has occurred, CPU module can be reset by a remote operation.

Enabling remote RESET

To remotely RESET, remote RESET must be enabled.
Navigation window  [Parameter]  [FX5UCPU]  [CPU Parameter]  "Operation Related Setting"  "Remote Reset
Setting"
Window
Displayed items
Item
Remote Reset

Method of execution of remote RESET

The following are the methods of execution of remote RESET.
Engineering tool method
Refer to the following.
GX Works3 Operating Manual
12 REMOTE OPERATION
108
12.3 Remote RESET
Y70
Y71
Y72
Description
Set whether or not to enable remote RESET.
The ON/OFF status of Y70 is determined by
the ON/OFF status of M20 in PAUSE status.
Turns OFF in PAUSE status.
Turns ON in PAUSE status.
Setting range
• Disable
• Enable
Default
Disable