5.2 b: Application
The PID acceleration/deceleration time can be canceled using a digital input programmed for "PID SFS cancel" (H1-oo =
34).
No.
b5-17
n
b5-18: PID Setpoint Selection
Enables or disables parameter b5-19 for PID setpoint.
Refer to
Figure 5.18
for the digital operator home screen display when PID is enabled and b5-18 is set to 1, enabling PID
Setpoint Selection.
- MODE -
PID Setpoint Cmd
U5-99= 30.00%
U5-01= 50.55%
U5-02= -50.55%
JOG
No.
b5-18
Setting 0: Disabled
Parameter b5-19 is not used as the PID setpoint.
Setting 1: Enabled
Parameter b5-19 is used as PID setpoint.
n
b5-19: PID Setpoint Value
Used as the PID setpoint if parameter b5-18 = 1.
Note:
Values set above b5-38 will be internally limited to b5-38.
No.
b5-19
u

EZ Sleep/Wake-up Function

To enable EZ Sleep/Wake-up functionality on the drive, first set parameter b5-89 to 1. The default setting for b5-89 is 0, which
disables the EZ Sleep functionality and related parameters, except for parameter b5-91, EZ Sleep Minimum Speed.
Setting b5-89 to 1 disables the existing PID Sleep function (b5-15) and enables the EZ Sleep/Wake-up functionality.
EZ Sleep and Minimum Speed Units
Parameter b5-90, EZ Sleep Unit, determines the unit, range, and resolution of parameters b5-92 and b5-93. When set to Hz,
the range is 0.1 to 400.0 Hz. When set to RPM, the range is 0 to 24000 RPM. Changing b5-90 will NOT automatically re-
scale the values of b5-92 and b5-93.
Minimum Speed
Parameter b5-91, EZ Minimum Speed, acts as a lower limit on the PID output. This value is internally limited to the higher
value between b5-34 or d2-02 and is active regardless of the b5-89 setting. When this limit is active, the PID integrator will
be held to avoid integral wind-up. Parameter b5-90 determines whether the value is input in Hz or RPM.
Sleep
When the output frequency (or speed) is at or below the EZ Sleep Level (b5-92) for the time set in EZ Sleep Time (b5-93),
the drive will sleep. The EZ Sleep Level is internally lower limited to the b5-92 setting.
Wake-up using Absolute Level (b5-95 = 0)
For Normal Acting PID, the PID Feedback must drop below the EZ Wake-up Level (b5-94) for the time set in EZ Wake-up
Time (b5-96) in order for the drive to wake-up.
168
Name
PID Accel/Decel Time
DRV RDY
ENTER
LSEQ
RREF
ESC
Figure 5.18 PID Setpoint Selection Display
Parameter Name
PID Setpoint Selection
Name
PID Setpoint Value
Setting Range
0.0 to 6000.0 s
- MONITR -
DRV RDY
PID Setpoint
b5-19= 030.00%
(0.00~100.00)
"0.00%"
Setting Range
0, 1
Setting Range
0.00 to 600.00%
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Default
0.0 s
ENTER
Default
0
Default
0.00%