Drive
Terminal
Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4o0180
p1, n1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4o0216
p1, n1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4o0240
p1, n1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4o0302
p1, n1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4o0361
p1, n1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4o0414
p1, n1
u

Main Circuit Terminal and Motor Wiring

This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should
match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to
comply may result in abnormal operation of drive and nearby equipment.
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
For USA and Canada
Recomm. Gauge
Wire Range
2
mm
mm
(AWG, kcmil)
(AWG, kcmil)
35 × 2
25 to 95 × 2
(2 × 2P)
(3 to 4/0 × 2P)
35 × 2
25 to 95 × 2
(2 × 2P)
(3 to 4/0 × 2P)
25
25 to 70
(3)
(4 to 2/0)
2.5
2.5 to 4
(14)
(14 to 12)
50 × 2
35 to 95 × 2
(1/0 × 2P)
(2 to 4/0 × 2P)
50 × 2
35 to 95 × 2
(1/0 × 2P)
(2 to 4/0 × 2P)
25
25 to 95
(3)
(4 to 4/0)
2.5
2.5 to 4
(14)
(14 to 12)
50 × 2
50 to 95 × 2
(1/0 × 2P)
(1/0 to 4/0 × 2P)
50 × 2
50 to 95 × 2
(1/0 × 2P)
(1/0 to 4/0 × 2P)
35
35 to 95
(2)
(2 to 4/0)
2.5
2.5 to 4
(14)
(14 to 12)
70 × 2
50 to 95 × 2
(3/0 × 2P)
(1/0 to 4/0 × 2P)
70 × 2
50 to 95 × 2
(3/0 × 2P)
(1/0 to 4/0 × 2P)
35
35 to 150
(1)
(1 to 300)
2.5
2.5 to 4
(14)
(14 to 12)
95 × 2
70 to 95 × 2
(4/0 × 2P)
(3/0 to 4/0 × 2P)
95 × 2
70 to 95 × 2
(4/0 × 2P)
(3/0 to 4/0 × 2P)
50
50 to 150
(1/0)
(1/0 to 300)
2.5
2.5 to 4
(14)
(14 to 12)
150 × 2
95 to 150 × 2
(300 × 2P)
(4/0 to 300 × 2P)
150 × 2
95 to 150 × 2
(300 × 2P)
(4/0 to 300 × 2P )
50
50 to 240
(1/0)
(1/0 to 400)
2.5
2.5 to 4
(14)
(14 to 12)
For South America
Recomm. Gauge
2
2
mm
(AWG, kcmil)
25 × 2P
(3 × 2P)
25 × 2P
(3 × 2P)
25
(3)
2.5
(14)
35 × 2P
(1 × 2P)
35 × 2P
(1 × 2P)
35
(1)
2.5
(14)
50 × 2P
(1/0 × 2P)
50 × 2P
(1/0 × 2P)
50
(1/0)
2.5
(14)
70 × 2P
(3/0 × 2P)
(1/0 to 4/0 × 2P)
70 × 2P
(3/0 × 2P)
(1/0 to 4/0 × 2P)
70
(3/0)
2.5
(14)
95 × 2P
(4/0 × 2P)
(3/0 to 4/0 × 2P)
95 × 2P
(4/0 × 2P)
(3/0 to 4/0 × 2P)
95
(4/0)
2.5
(14)
95 × 2P
(4/0 × 2P)
(4/0 to 300 × 2P)
95 × 2P
(4/0 × 2P)
(4/0 to 300 × 2P )
95
(4/0)
2.5
(14)
3.8 Main Circuit Wiring
Screw
Wire Range
Size
2
mm
(AWG, kcmil)
25 to 95 × 2P
M10
(3 to 4/0 × 2P)
25 to 95 × 2P
M10
(3 to 4/0 × 2P)
25 to 70
M10
(3 to 2/0)
2.5 to 4
M4
(14 to 12)
(10.4 to 17.4)
25 to 95 × 2P
M10
(3 to 4/0 × 2P)
25 to 95 × 2P
M10
(3 to 4/0 × 2P)
25 to 95
M12
(3 to 4/0)
2.5 to 4
M4
(14 to 12)
(10.4 to 17.4)
35 to 95 × 2P
M10
(1 to 4/0 × 2P)
35 to 95 × 2P
M10
(1 to 4/0 × 2P)
35 to 95
M12
(1 to 4/0)
2.5 to 4
M4
(14 to 12)
(10.4 to 17.4)
50 to 95 × 2P
M10
50 to 95 × 2P
M10
35 to 150
M12
(1 to 300)
2.5 to 4
M4
(14 to 12)
(10.4 to 17.4)
70 to 95 × 2P
M10
70 to 95 × 2P
M10
70 to 150
M12
(3/0 to 300)
2.5 to 4
M4
(14 to 12)
(10.4 to 17.4)
95 to 150 × 2P
M12
95 to 150 × 2P
M12
70 to 240
M12
(3/0 to 400)
2.5 to 4
M4
(14 to 12)
(10.4 to 17.4)
Tightening
Torque
N·m (lb.in.)
15 to 20
(130 to 173)
17.7 to 22.6
(156 to 200)
1.2 to 2.0
15 to 20
(130 to 173)
31.4 to 39.2
(278 to 347)
1.2 to 2.0
15 to 20
(130 to 173)
31.4 to 39.2
(278 to 347)
1.2 to 2.0
15 to 20
(130 to 173)
31.4 to 39.2
(278 to 347)
1.2 to 2.0
15 to 20
(130 to 173)
31.4 to 39.2
(278 to 347)
1.2 to 2.0
3
25 to 35
(217 to 304)
31.4 to 39.2
(278 to 347)
1.2 to 2.0