3 Installation
3.4 Electrical Installation

3.4.3 Connection to SmartWire-DT

3.4.3.1 PKE32-COM communication cable
82
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Connect the SWD external device plug with the adapted SmartWire-DT
ribbon cable.
SWD4-100LF8-24
SWD4-3LF8-24-2S
SWD4-5LF8-24-2S
SWD4-10LF8-24-2S
1
Figure 64: Connecting the SmartWire-DT external device plug with the adapted ribbon cable
NOTICE
Do not install or remove the SWD4-8SF2-5 SmartWire-DT
external device plug without switching off the supply and control
voltages first.
To connect a PKE motor-protective circuit-breaker (sizes 1 and 2 only) with a
PKE-XTU(W)A-... trip block to a DS7-SWD soft starter (size 1 or size 2), you
will need a PKE32-COM communications cable. This cable will serve as a
communication link between the DS7-SWD soft starter and the
PKE-XTU(W)A-... PKE trip block. Data will be exchanged via the PKE trip
block's data interface and the data interface on the DS7-SWD soft starter.
Figure 65: PKE32-COM communication cable
a Connector for PKE-XTU(W)A-... trip block
b Data cable with connector for soft starter DS7-SWD
2
SW D4 -8S F2- 5
S W D 4- 8S F2 -5
+ 15 V
+ 15 V
SWD4-8SF2-5