Eaton DS7 Manual page 24

Hide thumbs Also See for DS7:
Table of Contents

Advertisement

1 Device series DS7
1.7 Technical data
20
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
The motor outputs listed below can be connected when using single-phase
AC motors (asynchronous capacitor motors) and a load suitable for soft
starters within an industrial environment:
Table 5: Assigned rated motor outputs for AC motors
Part no.
Soft starter's rated
operational current
I
(IEC)
e
A
DS7-34xSX004N0-...
4
DS7-34xSX007N0-...
7
DS7-34xSX009N0-...
9
DS7-34xSX012N0-...
12
DS7-34xSX016N0-...
16
DS7-34xSX024N0-...
24
DS7-34xSX032N0-...
32
1) Motor shaft output for normal four-pole internal and surface-cooled AC motors
(1500 rpm at 50 Hz or 1800 rpm at 60 Hz)
2) IEC: Mains voltage = Motor voltage (at load) 230 V
3) Reduced overload current acc. to UL 508C
4) Mains voltage 208 V / 240 V ↔ motor voltage 200 V / 230 V
When using single-phase AC motors, the rated operational
current will depend on the system frequency and the capacitor
being used.
Example:
240 V, 50/60 Hz, 1.5/2.1 A
1300/1350 rpm, 5.0 μF CAP
Assigned motor output
2)
3), 4)
I
(UL)
230 V
e
50 Hz
A
kW
4.2
0.37
7.6
0.75
9.6
1.1
14
1.5
17.5
2.2
25.3
3
34
4
1)
at
200 V
208 V
230 V
60 Hz
60 Hz
60 Hz
HP
HP
HP
¼
½
½
¾
¾
1
1
1
2
2
2
3
3
3
5
5
5