8 SmartWire-DT
8.9 Programming
PNU
PNU
Access
Index
Sub-
rights
index
860
0
ro
190
Designation
Data type
Warnings
Unsigned32
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Meaning
Warnings
If bit WARN = 1 in profiles 7, 8, 9,
11, a warning is active. The
warning can be read in PNU 860.0.
Reading the warning will only be
possible as long as the warning is
active. Warning bits 16 to 24 will
only be generated if the error
response for the corresponding
fault is (PNU 840.X) = 1.
Example: PNU 860.0: Bit 20 = 1 →
Thyristor fault
0
2
: NoCurrentFeedback
(generated if current limiting
(PNU 681.0) is activated and the
DS7-SWD soft starter has the
RUN status.)
1
2
: OvertempForNextStart (the
heat sink is still too hot for a new
start; however, continuous
operation can be continued.)
2
2
: StartWithoutEnable (start
command active, but no EN signal
present yet)
16
2
: HeatsinkOverUnderTemp
(Heat sink overtemperature/
undertemperature)
17
2
: ElectronicsOverTemp
(Overtemperature Electronic)
18
2
: ThyristorOverTemp
2
(Overtemperature, thyristor (I
t))
19
2
: SupplyVoltageFault (Supply
voltage error)
20
2
: ThyristorFault (Thyristor error)
21
2
: BypassDefective (Bypass is
defective)
22
2
: PhaseLoss (phase failure)
23
2
: CommunicationFault
(erroneous communication)
24
2
: ExternalFault (external fault)
Value range
DS
0 - 4294967295
User
setting