8.9 Programming
8.9.3.10 Profile 10: Inputs (status)
178
Input bytes 0 and 1 (Short) are mapped as follows on SmartWire-DT.
Table 36: Profile 10: Input bytes 0 and 1
Byte
Bit
Designation
0
0, 1
2, 3
A1, A2
4
DIAG
5
6
PRSNT
7
SUBST
1
0
ERR
1
WARN
2
RDY
3
RUN
4
TOR
1)
5
CL
6, 7
1) Bit 5 will only be activated if parameter 681.0 is set to 1.
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Meaning
Not used
1-0-A switch on DS7:
00: not defined
10: Position A: Automatic (commands via
SmartWire-DT/control signal terminal)
01: Position 0: DS7 stop
11: Position 1: DS7 operation
0: no diagnostic alarm
1: Diagnostic alarm present
Not used
0: Device not present
1: Device present
0: Configured module present
1: universal module M22-SWD-NOP(C) present
Error present
0: no error
1: Error
Warning present:
0: no warning
1: Warning
Ready to operate, switched on
0: not switched on
1: switched on
DS7 running, power section active
(DS7 Run, power part active):
0: Stop (power section inactive)
1: Operation (power section active)
Top of ramp:
0: Top of start ramp not reached
1: Top of start ramp reached
Current limit:
0: Current limit not reached
1: Current limit reached
Not used