8 SmartWire-DT
8.9 Programming
8.9.5.3 cycle time
196
SmartWire-DT will require a certain amount of time in order to transmit data
to the DS7-SWD soft starter. Likewise, the DS7-SWD soft starter will require
a certain amount of time in order to perform the corresponding commands.
Following are a couple of examples showing response times for cyclic data
transfers and for the feedback signal sent back to the PLC.
Example 1:
XC202... controller, PROFIBUS DP interface, 2 slaves
Size
Set value
Baud Rate
500 kBaud at DP
250 kBaud at SWD
Start
150 - 200 ms
Stop
150 - 200 ms
Coast Stop
1.5 s (complete stop)
External Error
150 - 200 ms (complete stop)
Example 2:
XC202... controller, PROFIBUS DP interface, 58 slaves
Size
Set value
Baud Rate
9.6 kBaud at DP
125 kBaud at SWD
Start
600 ms
Stop
600 ms
Quick Stop
2 - 2.5 s
In the case of PROFIBUS DP, the decisive factor for response time is the
baud rate, not the number of slaves.
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com