3.3.2 Mounting instructions (BG 1 and BG 2)
3.3.2.1 Free surrounding areas
→
An installation clearance of 25 mm must be maintained in front
of size 1 and size 2 (up to 32 A) DS7 soft starters. A top and
bottom clearance of 75 mm each is required. If the clearances
are smaller, derating will be necessary or it will be necessary to
use the optional DS7-FAN-032 fan.
All sizes can be mounted directly next to each other.
Side clearance is not required to other devices that do not
themselves require clearance at the sides.
≧ 25 mm
(≧ 0.98")
≧ 25 mm
(≧ 0.98")
Figure 50: Installation clearances for devices up to 32 A
Top: Devices without SmartWire-DT; bottom: Devices with
SmartWire-DT
→
If the point if installation is subject to continuous vibration or
shocks, design measures must be taken for dampening, such as
through the use of vibration dampers.
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
3.3 Flush mounting in control panel
≧ 0
≧ 0
3 Installation
69