3 Installation

3.3 Flush mounting in control panel

3.3 Flush mounting in control panel
62
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
The mounting should take into account the weight and dimensions of the
soft starter. If necessary the appropriate technical resources (lifting cart or
crane for large weights) and tools must be used. Improper handling or use of
the wrong tools may cause damage to the soft starter.
The Soft starter DS7 is only designed for use as built-in device.
Take sufficient counter measures in the case of:
Contaminated cooling air, such as dust, fluff, grease:
This can cause short-circuits on the cards
(counter measures: installation of filters, separate ventilation circuit).
Aggressive gases:
These can corrode circuit-board conductors
(counter measures: flush mounting of filters, separate ventilation circuit).
Contaminated filters:
These can cause overheating (counter measure: regular cleaning).
To prevent overheating, observe the following points:
Ensure the free flow of the cooling air both to and from the device.
No devices that produce considerable amounts of heat in the proximity of
the soft starter.
Observe the mounting clearance above and below the soft starter as the
temperature of the cooling air will otherwise reach impermissible values
and the soft starter will switch off.
> ϑ
ϑ = -5... +40 °C
(ϑ = 23... +104 °F)
Figure 39: Cooling air supply