8.9.3.15 Profile 11: Outputs (control)
Output bytes 0 + 4 are mapped as follows on SmartWire-DT.
Table 39: Profile 11: Output bytes 0 + 4
Word
Bit
0
0
1
2
3
4
5
6
7
8
9
10
11 - 14
15
1
0 - 15
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Designation
Meaning
OnOff
Switch on/off
0: Normal stop (with configured ramp time)
1: Operation
Off2
Run-down (Coast Stop: Off 2)
0: Coast stop (switch off output voltage)
1: no free run-down
Off3
Quick Stop: Off3
0: Quick stop (shortest ramp)
1: no quick stop
EN_Op
Operation released
0: Stop
1: Operation
EN_Ramp
Enable Ramp
0: Reset ramp (setpoint value = 0)
1: Release ramp
Un-Freeze
Freeze ramp
0: Freeze ramp (the ramp generator's current output value
will be frozen)
1: Do not freeze ramp
EN_Set
Enable Setpoint, DS7 Start/Stop:
EN_Set enables the setpoint value and starts or stops
the motor with the ramp function.
0: Do not activate setpoint value
1: activate setpoint value
FaultAck
Fault Acknowledge
0: Do not acknowledge current fault
1: Acknowledge current fault (rising edge: 0 → 1)
Not used
Not used
Ctl_PLC
PLC assumes control (Control by PLC)
0: no control via PLC
1: Control via PLC
Not used
ExtFault
External Fault
If the bit is set, the DS7-SWD stops with a selected
PNU 840 function. The behavior is the same as for a
transition of the Enable signal from 1 to 0, except that soft
starter DS7-SWD switches to Error state (input bytes n + 4:
bit 3).
The external fault can be reset just like any other fault
(with Fault acknowledge (bit 7) or by switching the supply
voltage off and on).
0: no external fault
1: external fault
Transmit values of currents from PKE motor-protective
circuit-breaker to DS7 soft starter → section 8.9.3.14,
"Profile 11: outputs (transmitting external current values to
the DS7 soft starter, firmware V48 and higher)", page 181
8 SmartWire-DT
8.9 Programming
183