9.3.2 Terminal capacity, control cables, actuating circuit
The following technical data depends on size.
Size
General
Dimensions (W x H x D)
Weight
Terminal capacity
Cables
(box terminal)
Solid
Flexible with ferrule
Stranded
Solid or stranded
Flat conductor
minimum
maximum
Tightening torque
Control cables
Solid
Flexible with ferrule
Stranded
Solid or stranded
Tightening torque
Screwdriver (flat blade)
Actuating circuit
Relay outputs
Number
Max. voltage range
Max. load current
1) Does not apply for soft starter DS7 with SmartWire-DT (DS7-...-D).
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Unit
Frame size 1:
Frame size 2:
4 - 12 A
16 - 32 A
mm
45 x 130 x 95
45 x 150 x 118
kg
0.35
0.4
2
mm
1 x (0.75 - 4)
1 x (0.75 - 16)
2 x (0.75 - 2.5)
2 x (0.75 - 10)
2
mm
1 x (0.75 - 2.5)
1 x (0.75 - 16)
2 x (0.75 - 2.5)
2 x (0.75 - 10)
2
mm
1 x 16
2 x 16
AWG
1 x (18 - 10)
1 x (14 - 8)
2 x (18 - 10)
2 x (14 - 8)
mm
mm
Nm
1.2
3.2
2
mm
1 x (0.75 - 4)
1 x (0.75 - 4)
2 x (0.75 - 2.5)
2 x (0.75 - 1.5)
2
mm
1 x (0.75 - 2.5)
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
2 x (0.75 - 1.5)
2
mm
AWG
1 x (18 - 10)
1 x (18 - 14)
2 x (18 - 10)
2 x (18 - 16)
Nm
1.2
0.6
mm
0.6 x 3.5
0.6 x 3.5
1 (TOR)
2 (TOR,
RUN/READY)
V AC/DC
= U
250
s
A
1
1
9 Appendix
9.3 Specific technical data
Frame size 3:
Frame size 4:
41 - 100 A
135 - 200 A
93 x 175 x 139
108 x 215 x 178
1.8
3.7
1 x (25 - 70)
1 x (4 - 185)
2 x (6 - 25)
2 x (4 - 70)
1 x (25 - 70)
1 x (4 - 185)
2 x (6 - 25)
2 x (4 - 70)
1 x (12 - 2/0)
1 x (12 - 350 mcm
2 x (12 - 00)
2 x 9 x 0.8
2 x 9 x 0.8
9 x 9 x 0.8
10 x 16 x 0.8
9 (> 10 mm²)
14 (> 10 mm²)
6 (≦ 10 mm²)
5 (≦ 10 mm²)
1 x (0.75 - 4)
1 x (0.75 - 4)
2 x (0.75 - 1.5)
2 x (0.75 - 1.5)
1 x (0.75 - 2.5)
1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
2 x (0.75 - 1.5)
1 x (18 - 14)
1 x (18 - 14)
2 x (18 - 16)
2 x (18 - 16)
0.6
0.6
0.6 x 3.5
0.6 x 3.5
2 (TOR,
2 (TOR,
1)
1)
RUN/READY)
RUN/READY)
250
250
1
1
1)
217