2 Engineering
2.12 Loading conditions

2.12.4 Configuration options of DS7

Stand-alone setup
without internal fan
Stand-alone setup
of sizes 1 and 2
with internal fan
Assembly with
xStart components without fan
Assembly with
xStart components with fan
56
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Table 10: Configuration options
Special feature
Configuration
Standard setup
DS7
Increased number of
DS7 (to 32 A)
startups
+ DS7-FAN-032 (fan)
Derating required
DS7 (to 32 A)
+ PKZM0-XDM12 or
PKZM0-XM32DE, PKZ/PKE
DILM12-XMCP/T or
ZB...12/ZB32...
No derating required
DS7 (to 32 A)
+ PKZM0-XDM12 or
PKZM0-XM32DE, PKZ/PKE
DILM12-XMCP/T or
ZB...12/ZB32...
+ DS7-FAN-032 (fan)
• Increased number
DS7 (to 32 A)
of startups
+ PKZM0-XDM12 or
• Derating required
PKZM0-XM32DE, PKZ/PKE
DILM12-XMCP/T or
ZB...12/ZB32...
+ DS7-FAN-032 (fan)
Current
Starts
per hour
Rated operating current I
10
e
stated on the device applies.
Rated operating current I
40
e
stated on the device applies.
The next lower rated
10
operating current I
. applies.
e
The rated operational
10
current I
stated on the
e
device applies.
The next lower rated
40
operating current I
. applies.
e
Applicable graph
The graph applicable to this
load cycle (10 starts per hour)
applies.
→ Example I. (page 58)
The graph applicable to this
load cycle (10 starts per hour)
applies.
The number of starts per
hour must be multiplied by
the factor 4, i.e.
1, 10, 20 → 4, 40, 80
→ Example II. (page 58)
The valid graph for the
corresponding next smaller
2)
device type applies.
→ Example III. (page 58)
The graph applicable to this
load cycle (10 starts per hour)
applies.
→ Example IV. (page 58)
The valid graph for the
corresponding next smaller
2)
device type applies.
The number of starts per
hour must be multiplied by
the factor 4, i.e.
1, 10, 20 → 4, 40, 80
→ Example V. (page 58)