8 SmartWire-DT
8.9 Programming
8.9.2.8 Network – State diagram for profiles 7, 8, 9, 11
154
If profile 7, 8, 9, or 11 (Long) is used with PNU 928.0 = 1, the state diagram
shown below will apply.
In addition to the transition conditions shown below, the
Ctl_PLC bit needs to be set in the output byte.
For more information on the Ctl_Req and Ctl_PLC bits, see
→ section 8.9.3, "Cyclic data".
Power supply on
S1: Switching On Inhibited
Bit 6 = 1; Bit 0, 1, 2 = 0
Bit 0 = 0 (OnOff) and
Bit 1 = 0
Bit 1 = 1 (Off2) and
(Off2)
Bit 2 = 1 (Off3)
S2: Ready For Switching On
Bit 0 = 1; Bit 1, 2, 6 = 0
Bit 0 = 1 (OnOff)
S3: Switched On
Bit 0, 1 = 1; Bit 2, 6 = 0
Bit 1 = 0
(Off2)
Bit 3 = 1
(EN_Op)
Bit 0, 1, 2 = 1; Bit 6 = 0
Figure 121: State diagram: Network (profiles 7, 8, 9, 11)
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Bit 2 = 0 (Off3)
Standstill or
Bit 0 = 0 (OnOff)
Bit 3 = 0
(EN_Op)
S4: Operation
Standstill or
Bit 1 = 0
Bit 3 = 0
(Off2)
(EN_Op)
S5: Switching Off
(Quick Stop)
Bit 0, 1, 5 = 1; Bit 2, 6 = 0
Bit 3 = 0
Bit 2 = 0
(EN_Op)
(Off3)
S5: Switching Off
(Ramp Stop)
Bit 0, 1 = 1; Bit 2, 5, 6 = 0
Bit 0 = 1
Bit 0 = 0
Bit 2 = 0
(OnOff)
(OnOff)
(Off3)