8.9.8.4 SmartWire-DT write response(-) – Error
8.9.8.5 SmartWire-DT read response(-) – Error
This section shows the various possible device-specific errors that can occur
during communications via the acyclic parameter channel with PROFIBUS-DP.
The following table describes the various possible errors that can be
contained in the SmartWire-DT write response(-) – error.
Error Type
Failure code
Error_Code_1
A1
hex
Error_Code_1
A2
hex
Error_Code_1
B0
hex
Error_Code_1
B1
hex
Error_Code_1
B5
hex
In the case of XSoft-CoDeSys, only error code 54
listed above) can be output via function blocks XDPMV1_READ and
XDPMV1_WRITE when using a PROFIBUS-DP master.
For more information, see → section 8.9.6, "Acyclic parameter
channel for DS7-SWD soft starter", page 198.
This section shows the various possible device-specific errors that can occur
during communications via the acyclic parameter channel with PROFIBUS-DP.
The following table describes the various possible errors that can be
contained in the SmartWire-DT read response(-) – error.
Error Type
Failure code
Error_Code_1
A1
hex
Error_Code_1
A2
hex
Error_Code_1
B0
hex
Error_Code_1
B5
hex
In the case of XSoft-CoDeSys, only error code 54dec (representing the errors
listed above) can be output via function blocks XDPMV1_READ and
XDPMV1_WRITE when using a PROFIBUS-DP master.
For more information, see → section 8.9.6, "Acyclic parameter
channel for DS7-SWD soft starter", page 198.
For more information on the subject of acyclic data access
blocks for PROFIBUS-DP, consult manual MN05010002Z-EN,
"Function Blocks for XSoft-CoDeSys."
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Description
Write error: Only reading allowed for indexes 1 – 3 (PKE motor-protective
circuit-breaker).
DS7-SWD soft starter cannot be reached.
There is no valid index.
Parameter request block too long.
Parameter access temporarily not permissible due to internal processes.
Description
Write error: Only reading allowed for indexes 1 – 3
(PKE motor-protective circuit-breaker).
DS7-SWD soft starter cannot be reached.
There is no valid index.
Parameter access temporarily not permissible due to internal processes
8 SmartWire-DT