8.9.3.7 Profiles 7, 8, 9: Inputs (status)
Input bytes are mapped as follows on SmartWire-DT.
Table 34: Profiles 7, 8, 9: Input bytes
Byte
Bit
Designation
0
1
2
3
4
+2 (Long)
0
RSO
1
RDY
2
EN
3
ERR
4
C_Stop
5
Q_Stop
6
SOI
7
WARN
8
RUN
9
Ctl_Req
10
TOR
1)
11
CL
12
+2 (Long)
0 - 15
Utilization (Int16)
1) Bit 11 will only be activated if parameter 681.0 is set to 1.
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Meaning
→ section 8.9.3.2, "Inputs (status) profiles 1, 2, 3", page 161
Ready to switch on: S2
0: Not ready for switching on
1: Ready for switching on
Ready to operate; switched on: S3
0: not ready for operation
1: ready for operation
Operation (Enabled S4)
0: Stop
1: Operation
Error present (Error)
0: no error
1: Error
Free run-down, output de-energized (coast stop)
0: no free run-down
1: free run-down
Quick stop, shortest ramp
0: no quick stop
1: Quick stop
Reclosing lockout (switching on inhibited: S1)
0: No switch-on inhibit
1: Switch-on inhibit
Warning present:
0: no warning
1: Warning
DS7 Run, power part active
0: Stop (power section inactive)
1: Running (power section active)
Control requested to PLC
Is set if PNU 928.0 = 1.
0: Not ready for remote control
1: Ready for remote control
Top of ramp:
0: Top of start ramp not reached
1: Top of start ramp reached
Current limit:
0: Current limit not reached
1: Current limit reached
Not used
Load as a percentage (utilization %):
LB: Low Byte / HB: High Byte
0 - FFFF ≙ ±200 % / 0x4000 ≙ ±100 %