Potentiometer Settings; How The Potentiometers Work - Eaton DS7 Manual

Hide thumbs Also See for DS7:
Table of Contents

Advertisement

4 Operation

4.4 Potentiometer settings

4.4 Potentiometer settings

4.4.1 How the potentiometers work

98
The soft starters can be adjusted as necessary for the application at hand by
using the three potentiometers, which are labeled U-Start, t-Start, and
t-Stop respectively. Aside from these potentiometer settings, no additional
settings or prompts are required in order to run the soft starters.
When using DS7-SWD soft starters, these potentiometer settings can be
adjusted by means of parameters.
→ section 8.9, "Programming" explains how to configure the
DS7-SWD soft starter's parameters.
10
20
t-Start (s)
1
30
U-Start (%)
30
100
10
20
t-Stop (s)
0
30
Figure 70: Potentiometer layout
Table 17: Potentiometer settings in the default settings
Potentiometer
Value
U-Start
30 - 100 %
t-Start
1 - 30 s
t-Stop
0 - 30 s
U
U-Start
t-Start
Figure 71: Time-based control of motor voltage with a soft starter
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Function
Start voltage at which the ramp
function is started
Time in which the voltage is increased
from the value U-Start to 100 % with a
linear time ramp
Time in which the voltage is reduced
from 100 % to the value U-Start with a
linear time ramp
t-Stop
DS
PNU
Index
30 %
11
5 s
111
0 s
114
t
DS
4915
50
0