Eaton DS7 Manual page 181

Hide thumbs Also See for DS7:
Table of Contents

Advertisement

8.9.3.9 Profiles 7, 8, 9: Outputs (control)
Byte
0
+2 (DS7 status)
+2 (reserved)
Output bytes 0 and 4 are mapped as follows on SmartWire-DT.
Profiles 7, 8, and 9 correspond to profiles 1, 2, and 3, but with two added
words:
Profile 4 = Profile 1 (2 bytes) + DS7 status (2 words)
Table 35: Profiles 7, 8, 9: output bytes 0 and 4
Bit
Designation
0
OnOff
1
Off2
2
Off3
3
EN_Op
4
EN_Ramp
5
Unfreeze
6
EN_Set
7
FaultAck
8
9
10
Ctl_PLC
11 - 14
15
ExtFault
0 - 15
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Meaning
See: Profile 1 – 3: Output byte 0 → section 8.9.3.4, "Profiles 1, 2, 3:
Outputs (control)"
Switch on/off
0: Normal stop (with configured ramp time)
1: Operation
Run-down (Coast Stop: Off 2)
0: Coast stop (switch off output voltage)
1: no free run-down
Quick Stop: Off3
0: Quick stop (shortest ramp)
1: no quick stop
Operation released
0: Stop
1: Operation
Enable Ramp
0: Reset ramp (setpoint value = 0)
1: Release ramp
Unfreeze ramp
0: Freeze ramp (the ramp generator's current output value will be frozen)
1: Do not freeze ramp
Enable Setpoint, DS7 Start/Stop:
EN_Set enables the setpoint value and starts or stops the motor with the
ramp function.
0: Do not activate setpoint value
1: activate setpoint value
Fault Acknowledge
0: Do not acknowledge current fault
1: Acknowledge current fault (rising edge: 0 → 1)
Not used
Not used
PLC assumes control (Control by PLC)
0: no control via PLC
1: Control via PLC
Not used
External Fault
If the bit is set, the DS7 will stop with a selected PNU 840 function.
The behavior is the same as if there were a change from 1 → 0 in the Enable
signal, with the exception that the DS7 soft starter will switch to the
Error status (input bytes n + 4: bit 3).
The external fault can be reset just like any other fault (with Fault
acknowledge (bit 7) or by switching the supply voltage off and on).
0: no external fault
1: external fault
Not used
8 SmartWire-DT
8.9 Programming
177

Advertisement

Table of Contents
loading

Table of Contents