Eaton DS7 Manual page 191

Hide thumbs Also See for DS7:
Table of Contents

Advertisement

PNU
PNU
Access
Index
Sub-
rights
index
210
0
rw
280
0
ro
281
1
rw
290
0
ro
rw
(version
V48 and
higher)
310
0
ro
Designation
Data type
I
Unsigned16
m
I
Unsigned16
e
CurrentLimit
Unsigned16
IeBreakerMax
Unsigned16
Profiles
Unsigned16
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Meaning
Rated motor current I
from
m
nameplate:
X = I
x 10
m
X = Read/written value
Example:
Rated motor current: 2, 3 A
Value that the PLC needs to send:
23
The value is used to calculate the
current limit (PNU 281.1).
It must be sent by the PLC if it is
different from the DS7's rated
operational current I
. (I
is used
e
e
as a default setting.)
Soft starter rated operational
current I
:
e
X = I
x 10
e
X = Value read here
Current limitation:
A current limitation can be
implemented here by using a PKE.
If the configured limit value is
reached, the DS7-SWD will freeze
the voltage ramp and set the CL bit
in the SWD input byte (profiles 7,
to 9, and 11). PNU 681.0 activates
and deactivates the current
limitation. If the PKE does not
deliver any current, but PNU 681.0
= 1 and the DS7-SWD is running,
the DIAG2 bit will be set and, in
profiles 4 to 11, the WARN bit will
be set as well.
Rated motor current I
(PNU
m
210.0) is used for calculating the
current limitation within this
context. The value is independent
from the PKE motor-protective
circuit-breaker and from the DS7-
SWD soft starter model.
Maximum current of PKE:
X = I
Breaker x 10
e
X = Value read here
I
= 21.7 A; X = 217
e
Profile group being used
0: No selection
10: PROFIdrive profile
(Profiles 7, 8, 9, 11)
11: Short profile
(Profiles 4, 5, 6, 10)
12: Motor starter profile
(Profiles 1, 2, 3)
8 SmartWire-DT
8.9 Programming
Value range
DS
0 - 65535
0
0 - 200
0 - 800 %
300 %
65535
24576
0 - 650
0
0 - 12
10
User
setting
187