Simple Change Of Rotation - Eaton DS7 Manual

Hide thumbs Also See for DS7:
Table of Contents

Advertisement

7 Connection examples
7.1 Size 1 (4 – 12 A)

7.1.4 Simple change of rotation

122
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
L1
L2
L3
PE
Q1
I > I > I >
Q21
13 21
31
43
Q31
14 22
32
44
M
M1
3 ~
Figure 84:
Change of rotation
Example for accessories required:
S3 = M22-WRK... selector switch with three switch positions
Q31 = DILA-22(...) contactor + DILA... auxiliary contact module
When in the R position (FWD), S3 will use contact 23/24 to apply the enable
signal ① to the DS7 soft starter (+A1 control signal terminal). The rotation is
reversed with S3 via the zero position (off) to position L (REV).
The contactor Q31 is activated and switches the enable signal ① via the
auxiliary contact 53/54 to the DS7 soft starter (control terminal +A1).
(+) U
s
Q1
L O R
13
S3
14
Q31
(–) U
s
Figure 85:
Actuation of reversing contactor
TOR
+ U
- A2 + A1
13
s
(+) U
s
24 V AC/DC, 120/230 V AC
(–) U
s
23
24
53
54
Q1 = Cable and motor
protection
Q21 = Soft starter
Q31 = Reversing contactor
M1 = Motor
S3 = Rotation direction selection switch
with three contactor states
L = REV (anticlockwise rotating field)
0 = Off
R = FWD (clockwise rotating field)

Advertisement