8 SmartWire-DT
8.9 Programming
8.9.5.2 Acyclic DS7 soft starter data
PNU
PNU
Access
Index
Sub-
rights
index
Manufacturer Specific
11
0
rw
11
1
ro
12
0
rw
13
0
rw
14
0
rw
111
0
rw
111
1
ro
112
0
rw
113
0
rw
114
0
rw
114
1
ro
202
0
ro
203
0
ro
206
0
ro
186
The following table lists the various available parameters (PNUs). These
parameters are transmitted via the parameter channel described in the
following section.
Designation
Data type
U-Start
N2
U-StartPoti
N2
U-StartEnd
N2
U-StopStart
N2
U-Stop
N2
t-Start
T2
t-Start-Poti
T2
TOR-Delay
D2
Stop-Delay
D2
t-Stop
T2
t-StopPoti
T2
Device Name
OctetString
HW version
Unsigned16
Firmware Version
Unsigned16
(DS7-SWD)
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com
Meaning
Start voltage
Start voltage via potentiometer.
If local device control
(PNU 928=0), this value will
overwrite PNU 11.0.
U-start-end: The maximum ramp
voltage is reproduced here as a
percentage. Maximum reached:
100 %
U-stop-start: In the event of a soft
stop, the voltage will fall down to
the value set here; the stop ramp
will start
U-Stop: Minimum ramp voltage
(end of soft stop), minimum
reached = 0 %
Start time
Start time via potentiometer.
If local device control
(PNU 928=0), this value will
overwrite PNU 111.0.
Time between top of ramp and
TOR bit
Stop delay:
Time between TOR and start of
stop ramp
Stop Time
Stop time via potentiometer.
If local device control
(PNU 928=0), this value will
overwrite PNU 114.0.
DS7 designation
Hardware Version
Firmware Version
(DS7-SWD)
Value range
DS
30 - 100 %
30 %
4915 - 16384
4915
30 - 100 %
4915
4915 - 11468
30 - 100 %
100 %
4915 - 16384
16384
30 - 100 %
100 %
4915 - 16384
16384
30 - 100 %
30 %
4915 - 16384
4915
1 - 30 s
5 s
10 - 300
50
1 - 30 s
10 - 300
150 - 400 ms
150 ms
24576 - 65535
24576
150 - 400 ms
150 ms
24576 - 65535
24576
0 - 30 s
0 s
0 - 300
0
0 - 30 s
0 - 300
0 - 65535
0
0 - 65535
User
setting