Setting The Sinumerik Hmi Environment - Siemens SINUMERIK 810D Commissioning Manual

Hide thumbs Also See for SINUMERIK 810D:
Table of Contents

Advertisement

2.1.3

Setting the SINUMERIK HMI environment

Restoring the original HMI environment
The HMI environment is set to its original delivery condition. The content of the following
directories is saved prior to this:
● ADD_ON
● USER
● OEM
Then the directories are cleared.
Procedure
While the PCU is ramping up (after switching the controller off and then on again):
1. Select the Service menu [hidden menu entry] in the Boot Manager.
2. Press key <4>: Start Windows (Service Mode)
X
Your Choice [1, 4, 5, 9]?
3. Press key <4>.
4. Enter a password for authorization levels 0 - 2.
PCU Basesoftware (IM6)
Commissioning Manual, 10/2006, 6FC5397-0DP10-0BA0
The main menu is displayed.
The following menu is displayed:
PLEASE SELECT
1 Standard Windows (without starting SINUMERIK HMI)
4 Original SINUMERIK HMI environment
5 Current SINUMERIK HMI environment
9 Return to Main Menu
The system prompts you to enter a password:
Result:
The system will then restart automatically: The function is executed during the ensuing
start-up of Windows before the HMI system software is started.
Note
The original settings for the HMI environment can also be restored on the Service
desktop by starting the function "Original SINUMERIK HMI Environ".
Configuring the system
2.1 Service menu functions (DOS function)
2-5