Configuring the system
2.4 PCU with SITOP UPS module
"Fixed buffer time" mode
In this mode, the UPS module always buffers for the pre-selected, fixed period of time. It is
not possible to synchronize the UPS module with the operating system shutdown.
Required settings on the UPS module
2-22
On - Off
1
+2V
2
+1V
3
+0.5V
4
+1V
5
+1V
6
+0.5V
7
+0.2V
8
+0.2V
9
+0.1V
10
0.35A / 0.7A
On - Off
1
2
+320 s
3
+160 s
4
+80s
5
+40 s
6
+20 s
7
+10 s
8
9
Legend:
Cut-in threshold
+22V fixed
End-of-charge voltage
+26.3 V fixed
Charging current
Set time/max. time
Buffer time
+5 s fixed
Disconnection
Accumulator operating state on/off
Delivery condition setting
Setting for operation on the PCU 50
Commissioning Manual, 10/2006, 6FC5397-0DP10-0BA0