9-6 Specification for Operation Temperature and Protection Level

Model
Frame
230V: 0.75–22 kW
VFDxxxCxxx-21
460V: 0.75–30 kW
575V: 1.5~15 kW
690V: 18.5–37 kW
Frame
230V: ≥ 22 kW
VFDxxxCxxx-21
460V: ≥ 37 kW
690V: ≥ 45 kW
Frame
230V: ≥ 22 kW
VFDxxxCxxx-00
460V: ≥ 37 kW
690V: ≥ 45 kW
Top
Frame
cover
Top
A–C
cover
removed Standard
Standard
with top
cover
D0–H
N/A
D0–H
N/A
Chapter 9 Specification C2000 Plus
Conduit
Protection Level
Box
IP20 / UL Open Type
conduit
plate
IP20 / UL Type1 / NEMA1
Standard
conduit
IP20 / UL Type1 / NEMA1
box
IP00
IP20 / UL Open Type
No
conduit
box
Th e circled area: IP00
Oth er than the circled are a: IP20
9-13
Operation
Temperature
-10–50°C
-10–40°C
-10–40°C
-10–50°C
Figure 9-1
Table 9-10