F.1 FACTORY DEFAULT CONFIGURATION
NOTE:
SOURCE COLUMN:
This columns allow selecting the simple or complex (OR signal or Virtual output) operand that actives the selected
elements on relay configuration
If more than one operands are selected, the relay performs an OR gate with them to activate the selected element.
SIGNAL LOGIC COLUMN:
Refers to each individual signal selected on its left. NOT legend means that the refered signal is inverted
SOURCE LOGIC COLUMN:
Refers to the whole SOURCE signal selected on its left. NOT legend means that SOURCE signal is inverted
If more than one operand were selected, the OR gate output is inverted
SETPOINT>RELAY CONFIGURATION>OUTPUTS
OUTPUT ID
CONT OP OPER_F_01
CONT OP OPER_F_02
CONT OP OPER_F_03
CONT OP OPER_F_04
CONT OP OPER_F_05
CONT OP OPER_F_06
CONT OP OPER_F_07
CONT OP OPER_F_08
CONT OP OPER_G_01
CONT OP OPER_G_02
CONT OP OPER_G_03
CONT OP OPER_G_04
CONT OP OPER_G_05
CONT OP OPER_G_06
CONT OP OPER_G_07
CONT OP OPER_G_08
F
CONT OP RESET_F_01 Not Configured
CONT OP RESET_F_02 Not Configured
CONT OP RESET_F_03 Not Configured
CONT OP RESET_F_04 Not Configured
CONT OP RESET_F_05 Not Configured
CONT OP RESET_F_06 Not Configured
CONT OP RESET_F_07 Not Configured
CONT OP RESET_F_08 Not Configured
CONT OP RESET_G_01 Not Configured
CONT OP RESET_G_02 Not Configured
CONT OP RESET_G_03 Not Configured
CONT OP RESET_G_04 Not Configured
F-18
OUTPUT NAME
SOURCE
79 BLOCKED
AR BLOCK BY LEVEL
VO_046_59P_PKP
27/59 PKP
VO_045_27P_PKP
50/67G PKP
VO_048_50G_PKP
51/67G PKP
VO_049_51G_PKP
VO_051_50PH_PKP
50/67P PKP
VO_050_50PL_PKP
51/67P PKP
VO_053_51P_PKP
OPERATION BIT 1
RECLOSE
AR CLOSE BREAKER
OPERATION BIT 2
TRIP
VO_083_GENERAL_TRIP
81U/81O TRIP
VO_082_ALL_FREQUENCY_TRIP
27/59 TRIP
VO_079_ALL_OVERVOLTAGE_TRIP
50/67G TRIP
VO_068_50G_TRIP
51/67G TRIP
VO_067_51G_TRIP
VO_059_50PL_TRIP
50/67P TRIP
VO_058_50PH_TRIP
51/67P TRIP
VO_057_51P_TRIP
RCLS IN PROG
AR RCL IN PROGRESS
RCLS LOCKOUT
AR LOCKOUT
F650 Digital Bay Controller
F.1.2 FACTORY DEFAULT CONFIGURATION
SIGNAL
LOGIC
APPENDIX F
SOURCE
LOGIC