Metering; User-Programmable Front Keys; Current; Watt-Hours (Positive And Negative) - GE Multilin F650 Instruction Manual

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

2.4 TECHNICAL SPECIFICATIONS
e) USER-PROGRAMMABLE FRONT KEYS
Number of configurable Keys:
Operation:
2
a) CURRENT
Accuracy:
b) VOLTAGE
Accuracy:
c) REAL POWER (WATTS)
Accuracy:
d) REACTIVE POWER (VARS)
Accuracy:
e) APPARENT POWER (VA)
Accuracy:
f) WATT-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
Range:
Parameters:
Update rate:
g) WAR-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
Range:
Parameters:
Update rate:
h) POWER FACTOR
Accuracy:
Parameters:
2-20
5
drive PLC operands
±0.5% of the reading ± 10 mA from 0.05 to 10 A (for phases and ground)
±1.5% of the reading ± 1 mA from 0.005 to 5 A (for sensitive ground)
±1.5% of the reading for higher values
±1% reading ±0.1% Full Scale from 10 to 275 V
±1% of the reading at-0.8 < PF = -1 and 0.8 <PF=1
±1% of the reading at-0.2 = PF = 0.2
±1% of the reading
±1% of the reading
±0 to 2147 MWh
3-phase only
100 ms
±1% of the reading
±0 to 2147 MVArh
3-phase only
100 ms
0.02
3-Phase and single phase
F650 Digital Bay Controller
2 PRODUCT DESCRIPTION

2.4.5 METERING

GE Multilin

Advertisement

Table of Contents
loading