Iac Curves; Constants For Iac Curves - GE Multilin F650 Instruction Manual

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

5.4 PROTECTION ELEMENTS
5.4.2.3

IAC CURVES

This family of curves follows the time response of General Electric IAC electromechanical relays. The following formulas
define these curves:
Where:
t = Operation time in seconds
Dial = multiplier setpoint
I = Input current
Itap = Current pickup value
A, B, C, D, E = predefined constants
T
= reset time in seconds
RESET
5
t
= characteristic constant.
r
Table 5–32: CONSTANTS FOR IAC CURVES
IAC CURVE SHAPE
IAC Extremely Inverse
IAC Very Inverse
IAC Inverse
5-32
NAME
A
B
IAC Ext Inv
0.0040
0.6379
IAC Very Inv
0.0900
0.7955
IAC Mod Inv
0.2078
0.8630
F650 Digital Bay Controller
C
D
E
0.6200
1.7872
0.2461
0.1000
-1.2885
7.9586
0.8000
-0.4180
0.1947
5 SETPOINTS
TR
6.008
4.678
0.990
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents