F.1 FACTORY DEFAULT CONFIGURATION
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
SETTING DESCRIPTION
Setting Grouping Permission
Active Group
Snapshot Event generation
SETPOINT > CONTROL ELEMENTS > UNDERFREQUENCY
UNDERFREQUENCY 1 > UNDERFREQUENCY 2 > UNDERFREQUENCY 3
SETTING DESCRIPTION
Function permission
Pickup level
Trip time
Reset time
Minimum voltage threshold
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > OVERFREQUENCY
OVERFREQUENCY 1 > OVERFREQUENCY 2 > OVERFREQUENCY 3
SETTING DESCRIPTION
Function permission
Pickup level
Trip time
Reset time
Minimum voltage threshold
Snapshot event generation
F
F-14
NAME
DEFAULT VALUE
Function
DISABLED
Active Group
GROUP 1
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
49.50
Trip Delay
0.00
Reset Delay
0.00
Minimum Voltage
30
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
50.50
Trip Delay
0.00
Reset Delay
0.00
Minimum Voltage
30
Snapshot Events
ENABLED
F650 Digital Bay Controller
STEP
RANGE
N/A
[DISABLED – ENABLED]
[GROUP 1 – GROUP 2 –
N/A
GROUP 3]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 Hz
[20.00 : 65.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
1 V
[30 : 300]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 Hz
[20.00 : 65.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
1 V
[30 : 300]
N/A
[DISABLED – ENABLED]
APPENDIX F
USER
VALUE
USER
VALUE
USER
VALUE
GE Multilin