GE Multilin F650 Instruction Manual page 81

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
Table 4–2: TYPES OF FILES CREATED BY ENERVISTA 650 SETUP– ONLINE OPERATION MODE
FILE TYPE
SETTINGS & CONFIGURATION FILE *.650
Relevant
Protection Settings and
sections
Configuration Section
inside the file
Created by
EnerVista 650 Setup
Relay configuration file
containing all protection
Definition and
elements, settings, input/
contents
output and LEDs
configuration, graphic
display configuration, etc.
Connect with the relay ("Communications>Computer") Connect with the relay ("Communications>Computer")
4
Send settings and configuration from file:
Send protection and
control settings to relay:
"File>Send info to
relay", select *.650 file,
choose Protection and
Control settings option in
screen and press send
Basic
Modify settings and configuration directly in the relay:
information
transfer mode
to the relay
Go to "Setpoint>
>>Product Setup
>>System Setup
>>Protection Elements
>>Control Elements
>>Inputs/Outputs" in
EnerVista 650 Setup and
modify the selected
settings and press store
to send them to the relay.
EnerVista 650 Setup:
"File>Get info from
File storage in
relay". User definable
PC
texts retrieved are
operations, events, and
LEDs.
File storage inside the relay in a flash memory (RECOMMENDED):
File Retrieval of relay hard disk stored files (RECOMMENDED):
4-12
LOGIC CONFIGURATION FILES (*.PEP, *.AUT, *.LIB)
*.PEP
Compiled logic equations
Header for Logic
section (relay configuration
project
and logic configuration)
Logic configuration graphic
Logic configuration
editor (PLC Editor) and relay
graphic editor (PLC
configuration screen
Editor)
PLC project file
containing the
necessary
information relative
Equations corresponding to
to the relay model,
the logic created and
logic libraries
compiled in the PLC Editor
included in the
project (*.lib),
graphic file name
(*.aut), etc.
Launch 650 PLC Editor ("Setpoint>Logic Configuration")
Open the created PLC project ("File>Open Project")
Send configuration and logic
compiled equation to relay:
Compile the project ("Run>Compile")
"File>Send info to relay",
select *.650 file, choose
"Relay and Logic
Configuration" option in
screen and press send.
When the message
"Configuration stored"
appear in the relay HMI the
configuration has been
stored.
Go to "Settings>Relay
Configuration>
Now the logic (virtual outputs) can be sent directly to relay
>>Outputs
("Run>Send Equations to Relay"). Texts of virtual outputs are
>>LEDs
not stored in the relay, only in the logic configuration files to be
>>Operations
edited.
>>Protection Elements
>>Oscillography
>>Operations
>>Control Events
>>Switchgear
>>Inputs
>>Virtual Inputs
>>Operations
>>MMI (HMI)"
in EnerVista 650 Setup,
modify the selected values
and press store to send them
to the relay.
PLC Editor:
EnerVista 650 Setup:
"File>Save Project"
The relay provides this
information in a basic format
The relay will not
(compiled equations). It is
provide this
necessary to have the logic
information unless
configuration files used for
the *.pep file is
creating the PLC project to
stored in the relay
view the logic in a graphical
way (FDB) and be able to
To store the logic configuration files in the relay use the
modify it (virtual outputs).
"Communication>Upload info files to relay" option
"Communication>Upload info files to relay" through Ethernet
"Communication/Download info files from relay" through
Ethernet
F650 Digital Bay Controller
4 HUMAN INTERFACES
*.AUT
*.LIB
Graphical edition
container. Logic
User programmable
equations (Virtual
logic objects
Outputs) in FDB
format.
Logic configuration
Logic configuration
graphic editor (PLC
graphic editor (PLC
Editor)
Editor)
PLC Project file
Library file to be
containing all the
included as an object
drawings used by
in a PLC project.
the logic, required
Logic packages that
by F650 relay
can be stored into
based on IEC
libraries and be
61131-3 standard.
distributed in different
Functional block
PLC projects.
diagram (FDB).
"File>Save Library"
The relay will not
The relay will not
provide this
provide this
information unless
information unless
the *.pep file is
the *.pep file is stored
stored in the relay.
in the relay.
GE Multilin

Advertisement

Table of Contents