Voltages - GE Multilin F650 Instruction Manual

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

9 COMMISSIONING
9.7VERIFICATION OF MEASURE
Set the relay as follows
GENERAL SETTINGS
NAME
PHASE CT RATIO
GROUND CT RATIO
STV GROUND CT RATIO
PHASE VT RATIO
PHASE VT CONNECTION
NOMINAL VOLTAGE
NOMINAL FREQUENCY
PHASE ROTATION
FREQUENCY REFERENCE
AUXILIARY VOLTAGE
NOTE:
ALL ANGLES INDICATED ARE DELAY ANGLES
ALL VALUES OBTAINED IN THIS TEST MUST BE THE ONES CORRESPONDING TO THE DFT
Apply the following current and frequency values to the relay:
CHANNEL
VI
VII
VIII
VX
Verify that the relay measures the values with an error of +/-1 % of the applied value plus 0,1% of full scale (275V).
Apply the following voltage and frequency values to the relay:
CHANNEL
Ia (A)
Ib (A)
Ic (A)
IG(A)
ISG(A)
Verify that the relay measures the values with an error lower than +/-0.5% of the test value or+/- 10 mA, whichever is
greater, for phases and ground.
Verify that the relay measures the values with an error lower than +/-1.5% of the test value or+/- 1 mA, whichever is greater,
for sensitive ground (SG).
GE Multilin
VALUE
UNITS
1.0
0.1
1.0
0.1
1.0
0.1
1.0
0.1
WYE
N/A
100 V
0.1
50 Hz
1 Hz
ABC
N/A
VI
N/A
VX
N/A
ANGLE
FREQUENCY
50 Hz
60 Hz
0
5
120º
0
5
240º
0
5
0
5
ANGLE
FREQUENCY
50 Hz
60 Hz
45º
0
15
165º
0
15
285º
0
15
0
15
0
5
F650 Digital Bay Controller
9.7 VERIFICATION OF MEASURE
RANGE
1.0-6000.0
1.0-6000.0
1.0-6000.0
1.0-6000.0
WYE – DELTA
1-250 V
50-60 Hz
ABC – ACB
VI-VII-VIII
VX – VN
50 Hz
60 Hz
50 Hz
60 Hz
50
100
150
275
50
100
150
275
50
100
150
275
50
100
150
275
50 Hz
60 Hz
50 Hz
60 Hz
10
5
1
0.1
10
5
1
0.1
10
5
1
0.1
10
5
1
0.1
1
0.1
0.01
0.005

9.7.1 VOLTAGES

9.7.2 PHASE CURRENTS
9-7
9

Advertisement

Table of Contents
loading

Table of Contents