9 COMMISSIONING
9.8INPUTS AND OUTPUTS
During all tests, the screw on the rear of the relay must be grounded.
During this test, the user will determine the activation/deactivation points for every input in the relay for the set voltage value
of 30 Volts.
Verify that the error does not exceed +/- 10% (+10% on activation, -10% on deactivation)
Default board settings for the input test can be modified in EnerVista F650 Setup software in:
Settings>Inputs/Outputs>Contact I/O>Board X
X, will be substituted by the corresponding board:
F for board in first slot
G for board in second slot
H for board in first slot of CIO module
J for board in second slot of CIO module
Test settings for mixed board (type 1:16 inputs and 8 outputs) :
I/O BOARD TYPE 1 (MIXED)
Voltage Threshold A_X
Voltage Threshold B_X
Debounce Time A_X
Debounce Time B_X
Input Type_X_CC1 (CC1)
...
Input Type_X_CC16 (CC16)
The inputs test is completed by groups of 8 inputs, as this type of board has 2 groups of 8 inputs with the same common.
For the first 8 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 8 inputs, the setting
is Voltage Threshold B. Inputs (or contact converters, CC1 – CC16) must also be set to POSITIVE.
Test settings for mixed board (type 2: 8 digital inputs, 4 blocks for supervision and 8 outputs) :
I/O BOARD TYPE 2 (SUPERVISION)
Voltage Threshold A_X
Voltage Threshold B_X
Debounce Time A_X
Debounce Time B_X
Input Type_X_CC1 (CC1)
...
Input Type_X_CC8 (CC8)
The inputs test is completed by groups of 4 inputs, as this type of board has 2 groups of 4 inputs with the same common.
For the first 4 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 4 inputs, the setting
is Voltage Threshold B. Inputs (or contact converters, CC1 – CC8) must also be set to POSITIVE.
If the relay incorporates more input modules, this test must also be applied to them.
GE Multilin
30 V
40 V
5 ms
5 ms
POSITIVE
...
POSITIVE
30 V
40 V
5 ms
5 ms
POSITIVE
...
POSITIVE
F650 Digital Bay Controller
9.8 INPUTS AND OUTPUTS

9.8.1 DIGITAL INPUTS