APPENDIX F
SETPOINT > CONTROL ELEMENTS > SYNCHROCHECK
SETTING DESCRIPTION
Function permission
Dead bus voltage level
Live bus voltage level
Dead line voltage level
Live line voltage level
Voltage Difference
Angle Difference
Frequency Slip
Breaker Closing time
Dead Line – Dead Bus Function
permission
Live Line – Dead Bus Function
permission
Dead Line – Live Bus Function
permission
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > AUTORECLOSE
SETTING DESCRIPTION
Function permission
Maximum Number of shots
Dead time 1
Dead time 2
Dead time 3
Dead time 4
Reclaim time or reset lockout delay
Reclose conditions permission
Hold time
Reset time
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > VT FUSE FAILURE
SETTING DESCRIPTION
Function permission
Snapshot event generation
SETPOINT > CONTROL ELEMENTS > LOCKED ROTOR
BROKEN CONDUCTOR 1 >BROKEN CONDUCTOR 2 >BROKEN CONDUCTOR 3
SETTING DESCRIPTION
Function permission
Tap Level in percentage of I2/I1
Trip Time
Snapshot event generation
Current Inhibition Level setting
GE Multilin
NAME
DEFAULT VALUE
Function
DISABLED
Dead Bus Level
10.00
Live Bus Level
50.00
Dead Line Level
10.00
Live Line Level
50.00
Max Volt Difference
10.00
Max Angle Difference 10.0
Max Freq Difference
20
Time
0.50
DL-DB Function
DISABLED
LL-DB Function
DISABLED
DL-LB Function
DISABLED
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Max Number Shots
1
Dead Time 1
0.00
Dead Time 2
0.00
Dead Time 3
0.00
Dead Time 4
0.00
Reclaim Time
0.00
Cond. Permission
DISABLED
Hold Time
0.00
Reset Time
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Tap
20
Trip Delay
60
Snapshot Events
ENABLED
Operation Threshold
0.005
F650 Digital Bay Controller
F.1 FACTORY DEFAULT CONFIGURATION
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 V
[0.00 : 300.00]
0.01 V
[0.00 : 300.00]
0.01 V
[0.00 : 300.00]
0.01 V
[0.00 : 300.00]
0.01 V
[2.00 : 300.00]
0.1 Deg
[2.0 : 80.0]
10 mHz
[10 : 5000]
0.01 s
[0.01 : 600.00]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[1 : 4]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.10%
[20.0 : 100.0]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
0.001 A
[0.000 : 1.000]
USER
VALUE
USER
VALUE
USER
VALUE
F
USER
VALUE
F-15