Plc Logic; Flexcurves; User -Programable Elements - GE Multilin F650 Instruction Manual

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
a) PLC LOGIC
Programming language:
Lines of code:
Supported operations:
Libraries:
Inputs:
Number of timers:
b) FLEXCURVES
Number:
Reset points:
Operate points:
Time delay:
Saturation Level
c) USER-PROGRAMMABLE LEDS
Number:
Programmability:
Reset mode:
Reset Signal:
d) USER-DEFINABLE DISPLAYS
Number of configurable displays:
Number of fixed displays:
Number of selectable displays:
GE Multilin
The logical configuration is performed using graphical functions based on the
IEC 61131-3 standard.
512
NOT, XOR, OR (2 to 8 inputs), AND (2 to 8 inputs), NOR (2 to 8 inputs),
NAND (2 to 8 inputs), Latch (Reset Dominant), Edge Detectors, Timers.
2 inputs default gates, from 3 to 8 inputs provided in library format.
Logical gates fully programmable by user. To create user-programmable logic to
be distributed as a single object.
Any logical variable, contact or virtual input
8 maximum in each logic scheme (provided in library format)
4 (A through D)
40 (0 through 1 of pickup)
80 (1 through 20 of pickup)
0 to 65535 ms in steps of 1
20 times the pickup level
15 configurable LEDs plus a ready non configurable LED
from any logical variable, contact, or virtual input
Self-reset or Latched.
The first 5 LED's are latched by hardware (red color ones), usually configured for
trip signals.
The following 10 ones (yellow and green) are self-reset but can be latched
through PLC configuration.
The LED's can be reset by hardware, pressing the front "esc" key during more
than 3 seconds or using the LED reset signal through PLC configuration.
1 (one line diagram fully configurable). In graphical displays only
6, Metering (in primary values), Snapshot events (all and new), Alarms, Inputs
and outputs screen with test functionality for inputs and outputs. In graphical dis-
plays only
Logotype, metering or both in scrolling mode, can be selectable as default
screen in text display for all models (basic and mimic). The metering screen con-
tains current and voltages for phases and ground in primary values.
F650 Digital Bay Controller
2.4 TECHNICAL SPECIFICATIONS
2.4.4 USER –PROGRAMABLE ELEMENTS
2
2-19

Advertisement

Table of Contents
loading