F.1 FACTORY DEFAULT CONFIGURATION
SETPOINT > CONTROL ELEMENTS > LOCKED ROTOR
LOCKED ROTOR 1 >LOCKED ROTOR 2 >LOCKED ROTOR 3
SETTING DESCRIPTION
Function permission
Input type
Full load current
Pickup level
Trip time
Reset time
Snapshot event generation
SETPOINT > INPUTS/OUTPUTS > CONTACT I/O >
BOARD F > BOARD G > BOARD H > BOARD J
SETTING DESCRIPTION
I/O board type (available only for CIO
modules)
Input activation voltage threshold
Group A
Input activation voltage threshold
Group B
Debounce time for Group A
Debounce time for Group B
Input type
Input signal time delay
Output logic type
Output type
Output pulse length
Snapshot event generation
F
F-16
NAME
DEFAULT VALUE
Function
DISABLED
Input
PHASOR(DFT)
Full Load Current
0.5
Pickup Level
1.01
Trip Delay
0
Reset Delay
0
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
I/O Board Type_H
NONE
Voltage Threshold
80
A_X
Voltage Threshold
80
B_X
Debounce Time A_X
15
Debounce Time B_X
15
Input Type_X_CCY
POSITIVE
(CCY)
Delay Input
0
Time_X_CCY (CCY)
Output Logic_X_0Z
POSITIVE
Output Type_X_0Z
NORMAL
Pulse Output
10000
Time_X_0Z
Snapshot Events
ENABLED
F650 Digital Bay Controller
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[PHASOR – RMS]
KA
[0.10 : 10.00]
N/A
[1.01 : 109.00]
s
[0.00 : 900.00]
s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
[NONE,
N/A
16 INP + 8OUT,
8 INP + 8OUT + SUPV]
1 V
[0 : 255]
1 V
[0 : 255]
1 ms
[1 : 50]
1 ms
[1 : 50]
[POSITIVE-EDGE,
NEGATIVE-EDGE,
N/A
POSITIVE,
NEGATIVE]
1 ms
[0 : 60000]
[POSITIVE,
N/A
NEGATIVE]
[NORMAL,
N/A
PULSE,
LATCH]
1 ms
[0 : 60000]
N/A
[DISABLED – ENABLED]