GE Multilin F650 Instruction Manual page 500

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

APPENDIX F
SETPOINT > PROTECTION ELEMENTS > NEUTRAL CURRENT > NEUTRAL TOC
NEUTRAL TOC 1> NEUTRAL TOC 2 > NEUTRAL TOC 3
SETTING DESCRIPTION
Function permission
Pickup level
Curve shape
Time Dial
Reset type
Snapshot Event generation
SETPOINT > PROTECTION ELEMENTS > NEUTRAL CURRENT > NEUTRAL IOC
NEUTRAL IOC 1> NEUTRAL IOC 2 > NEUTRAL IOC 3
SETTING DESCRIPTION
Function permission
Pickup level
Trip time
Reset time
Snapshot event generation
SETPOINT > PROTECTION ELEMENTS > NEUTRAL CURRENT > NEUTRAL DIRECTIONAL >
NEUTRAL DIRECTIONAL 1> NEUTRAL DIRECTIONAL 2 > NEUTRAL DIRECTIONAL 3
SETTING DESCRIPTION
Function permission
Maximum Torque Angle
Operation Direction
Polarization type
Block logic type
Polarization voltage threshold
Snapshot event generation
SETPOINT > PROTECTION ELEMENTS > GROUND CURRENT > GROUND TOC
GROUND TOC 1> GROUND TOC 2 > GROUND TOC 3
SETTING DESCRIPTION
Function permission
Input type
Pickup level
Curve shape
Time Dial
Reset type
Snapshot Event generation
GE Multilin
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
1.00
Curve
IEEE Ext Inv
TD Multiplier
1.00
Reset
INSTANTANEOUS
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
30.00
Trip Delay
0.00
Reset Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
MTA
-45
Direction
FORWARD
Polarization
VO
Block Logic
PERMISSION
Pol V Threshold
10
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Input
PHASOR(DFT)
Pickup Level
1.00
Curve
IEEE Ext Inv
TD Multiplier
1.00
Reset
INSTANTANEOUS
Snapshot Events
ENABLED
F650 Digital Bay Controller
F.1 FACTORY DEFAULT CONFIGURATION
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 A
[0.05 : 160.00]
N/A
[See list of curves]
0.01 s
[0.00 : 900.00]
[INSTANTANEOUS –
N/A
LINEAR]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
0.01 A
[0.05 : 160.00]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 Deg
[-90 : +90]
N/A
[FORWARD – REVERSE]
[V
– I
– V
+I
– V
N/A
0
P
0
P
N/A
[BLOCK – PERMISSION]
1 V
[0 : 300]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[PHASOR – RMS]
0.01 A
[0.05 : 160.00]
N/A
[See list of curves]
0.01 s
[0.00 : 900.00]
[INSTANTANEOUS –
N/A
LINEAR]
N/A
[DISABLED – ENABLED]
USER
VALUE
USER
VALUE
USER
VALUE
*I
]
0
P
USER
VALUE
F
F-9

Advertisement

Table of Contents
loading

Table of Contents