General Overview Of Status Menu; Different Control Actual Values Included In The Control Elements Menu - GE Multilin F650 Instruction Manual

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
Table 4–17: GENERAL OVERVIEW OF STATUS MENU:
STATUS
4
Table 4–18: DIFFERENT CONTROL ACTUAL VALUES INCLUDED IN THE CONTROL ELEMENTS MENU
CONTROL
4-28
Up to 24 elements. OPERATION BIT XX is (0) when the configured time
Operation bits
out for the operation XX expires or when success conditions are met.
And it is (1) if operation XX is executed and interlocks are fulfilled.
Breaker status (open, closed or undefined). The rest of the status signals
Breaker
corresponding to the switchgear XX configured as breaker are in the
"Status>Switchgear Status>Switchgear XX" menu.
Protection
Status of all the protection units in the device.
Control Elements
Status of all the control units available in the device.
This screen shows a complete list of all protection and control elements
Protection Summary
in the relay, showing their status (enabled or not).
Snapshots events
Summary of the snapshot events status (enabled or disabled) for
summary
protection, control, inputs and outputs boards and switchgear.
Up to 256 elements. Value in SIGNED INT 16 BIT format of the reading
ModBus User Map
for the selected address configured in "Settings>Product
Setup>ModBus User Map"
Up to 16 blocks of switchgear status signals for the 16 configurable
devices. Status signals such as inputs for A and B contacts, status for A
Switchgear Status
and B, open and close status, error 00 and error 11, open init and close
init, fail to open and fail to close signals.
Internal states for calibration. Factory calibration and calibration error
Calibration
signals.
Flex curve status for A, B, C and D user curves. (0) if it is not configured,
Flex Curves
(1) if it is configured. To configure a flex curve go to "Settings>System
Setup>Flex Curves" menu.
This screen can monitor the system parameters and the internal status of
System Info
the Relay boot code. Not enabled by default, password required
Information related to the different records stored in the Relay, such as:
Records Status
Fault reports, control events, oscillography, data logger, demand, energy,
and breaker maintenance.
SNTP-IRIG-B
Information related to synchronization via IRIG_B or SNTP
Frequency
Status signals (pickups and operations) for under and overfrequency
units.
Synchrocheck
Status signals for synchrocheck function (25).
Autoreclose
Status signals for autoreclose function (79). Close signal, recloser status
(ready, lockout, etc), block signals after each shot.
Breaker Failure
Status signals for breaker failure function (50BF).
VT Fuse Failure
Fuse failure detection signal.
Broken Conductor
Status signals (pickups and operations) for broken conductor (I2/I1).
Setting Groups
Status signals (activations and blocks) for the relay setting group change.
By default the "setting group" setting is disabled and all the grouped
elements can be enabled at the same time.
Locked Rotor
Status signals (pickups and operations) for locked rotor units.
F650 Digital Bay Controller
4 HUMAN INTERFACES
GE Multilin

Advertisement