8.2 BOOT CODE UPDATE
8 BOOTCODE AND FIRMWARE UPDATE
Figure 8–13: ERASING FLASH MEMORY
Once the memory has been erased and the files updated in the relay, the parameters for the Ethernet communications
parameters must be assigned (Figure 8–14:). The requested values are the IP address and the gateway
Figure 8–14: ETHERNET PARAMETERS
These values should match the LAN structure in which the relay will be connected.
The gateway must be the one used in the LAN structure connecting the relay. The relay IP address should have the first
three octets corresponding with the Gateway and the last octet must be a free IP address reserved to the relay to avoid
possible collisions with other devices.
After assigning the Ethernet parameters, the update of the boot memory program has been completed successfully .
8
Figure 8–15: BOOT PROGRAM UPDATED
After boot memory update, the equipment firmware must also be updated (Section 8.3).
8-8
F650 Digital Bay Controller
GE Multilin